Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM00948
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/23/2011 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 05/23/2011 | DAVE MANN | FIRE | REVIEW | Denied | Fire Comments: A flow test is required to verify 2000 gpm is available from the hydrant across the street. The 4867 sqft would require this or automatic fire sprinklers need to be installed. Please call 837-7029 or 837-7030 to schedule a test. |
| 06/03/2011 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 06/06/2011 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/08/2011 | SUE REEVES | OUT TO CUSTOMER | Completed |
| 06/08/2011 | SUE REEVES | REJECT SHELF | Completed |