04/29/2011 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 4-29-11
Activity: T11CM00948
Address: 520 S Avenida De Palmas
Applicant: Interior Trends

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide emergency escape/rescue opening for basement, R310.

PLUMBING PLAN:
1. Specify minimum 1" water meter for proposed demand, Table P2903.6(1).

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review
05/06/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A8; FLOOR FRAMING PLAN (NOTE FOR PARALLAM BEAM): A NOTE AT THE 7" PARALLAM BEAM AT THE DECK AND GUEST ROOM INDICATES THERE IS A 3 1/2" PARALLAM BEAM TO BE CONNECTED WITH 1/4" X 6" LAG SCREWS. WHERE IS THIS 3 1/2" BEAM INDICATED IN THE DESIGN CALCULATIONS OR ON THE DRAWING SECTIONS? CLARIFY.
2. SHEET A8; FLOOR TRUSS NOTES: SHOULD THE NOTE UNDER THIS SECTION DELETE THE WORD "LIVE" AND READ MAXIMUM TOTAL LOAD DEFECTION LIMIT L/360? VERIFY.
3. SHEET A8; DETAIL 2: REMOVE THE REFERENCE R311.6.2 FROM THE STAIR LANDING WIDTH NOTE (THIS IS FOR A RAMP LANDING).
4. SHEETS A9/A10; UNVENTED ATTIC BOXED NOTE: HAS THIS BEEN APPROVED BY THE CITY OF TUCSON BUILDING OFFICIAL AS PER R104.11? PROVIDE APPROVAL LETTER.
5. SHEET A9; ROOF TRUSS NOTE: SHOULD THE LAST NOTE UNDER THIS SECTION DELETE THE WORD "LIVE" AND READ MAXIMUM TOTAL LOAD DEFECTION LIMIT L/240? VERIFY.
6. SHEET A10; DETAIL 9: A NOTE ON THE DETAIL INDICATES TO "SEE SHEET SD2 FOR FOUNDATION CONNECTION DETAIL". DID NOT LOCATE THAT DETAIL. VERIFY.
7. SHEET S1; LOWER FLOOR: SECTION CUT 3/SD3 AT THE MECHANICAL ROOM/PORCH INDICATES NO EXTERIOR SLAB AT THE PORCH. VERIFY.
8. SHEET SD1; DETAIL 4: THERE ARE TWO DETAIL 4'S ON THIS SHEET. REVISE. WHERE IS THIS DETAIL CUT ON THE PLAN?
9. SHEET SD2; DETAIL 4: THE NOTE INDICATING TRUSS BLOCKING DETAIL 6/SD3 IS INCORRECT. REVISE.
10. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.