Review Date Reviewer's Name Type of Review Description Status Comments
03/30/2011 DAVE MANN FIRE REVIEW Approved
04/07/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A12; GENERAL NOTES: REVISE NOTE A.
2. SHEET A12; WALL TYPES: WALL TYPE W2 IN THE RESTROOMS MUST MEET REQUIREMENTS OF THE 2006 IBC, SECTION 1210.2, FOR MOISTURE RESISTANCE. VERIFY.
3. SHEET A12 (FLOOR PLAN); SHEET A32 (ELEVATION A4): THE FLOOR PLAN INDICATES A SINK IN THE BREAK ROOM COUNTER, BUT THE ELEVATION SHOWS NO SINK. CLARIFY.
4. SHEET A12 (FLOOR PLAN); SHEET A32 (ELEVATION A4): WHERE IS THE REFERENCE TO THIS ELEVATION ON THE PLAN? VERIFY.
5. SHEET A32; ELEVATION A4 AND SECTION B3: WITH A SINK IN THE BREAK ROOM, THE SINK MUST BE ACCESSIBLE PER ICC/ANSI A117.1-2003, SECTIONS 804.4 AND 606.3, AND PER 2006 IBC, SECTION 1109.3. VERIFY AND REVISE COUNTER HEIGHT AS REQUIRED.
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
04/11/2011 GERRY KOZIOL WWM REVIEW Approved
04/18/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/18/2011 ROBERT SHERRY WATER REVIEW Approved
04/18/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/22/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved