Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM00915
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/30/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
04/07/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A12; GENERAL NOTES: REVISE NOTE A. 2. SHEET A12; WALL TYPES: WALL TYPE W2 IN THE RESTROOMS MUST MEET REQUIREMENTS OF THE 2006 IBC, SECTION 1210.2, FOR MOISTURE RESISTANCE. VERIFY. 3. SHEET A12 (FLOOR PLAN); SHEET A32 (ELEVATION A4): THE FLOOR PLAN INDICATES A SINK IN THE BREAK ROOM COUNTER, BUT THE ELEVATION SHOWS NO SINK. CLARIFY. 4. SHEET A12 (FLOOR PLAN); SHEET A32 (ELEVATION A4): WHERE IS THE REFERENCE TO THIS ELEVATION ON THE PLAN? VERIFY. 5. SHEET A32; ELEVATION A4 AND SECTION B3: WITH A SINK IN THE BREAK ROOM, THE SINK MUST BE ACCESSIBLE PER ICC/ANSI A117.1-2003, SECTIONS 804.4 AND 606.3, AND PER 2006 IBC, SECTION 1109.3. VERIFY AND REVISE COUNTER HEIGHT AS REQUIRED. 6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
04/11/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
04/18/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
04/18/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/18/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
04/22/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved |