Review Details: COMMERCIAL - TI

Permit Number - T11CM00914
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
03/29/2011 ANY ZONING REVIEW Active
03/29/2011 ANY WWM REVIEW Active
03/29/2011 ANY ELECTRICAL-COMMERCIAL REVIEW Active
03/29/2011 ANY ENGINEERING REVIEW Active
03/29/2011 ANY BUILDING-COMMERCIAL REVIEW Active
03/29/2011 Any ADA REVIEW Active
03/29/2011 ANY FIRE REVIEW Active
03/29/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Active
04/21/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/21/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the drain and vent for each lavatory is to be modified if the current installation uses a wet vent arrangement.
2. Clarify the drainage piping for the mop sink, 3-compartment sink, and the floor sink with regard to the grease interceptor. External flow control devices shall be visible and readily accessible (i.e. not below grade).
04/21/2011 ROBERT SHERRY WATER REVIEW Approved