Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/WWM
Permit Number - T11CM00890
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/22/2011 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL REQUIREMENTS: Show corrections and revisions on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and notate sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review. All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration. FLOOR PLANS: 1. Show that each water closet is located in a clear space not less than 30" wide (centered 15" from finished wall or fixture) and has a clear space in front not less than 24", R307.1 & UPC 407.6. 2. Show the remaining Bedroom #3 window is in compliance with R310 providing egress. 3. Show the location of an existing or proposed minimum 22" x 30" attic access. Also show passage between the proposed and accessible existing and attic areas. STRUCTURAL PLANS: 1. Notate a proposed location and weight of the HVAC load on the roof framing plan for verifying the truss load carrying capacity used for the engineered truss design, R301.1 & M1401. SECTIONS - DETAILS: 1. Calculate and show the attic ventilation using 1 to 150 of attic area in compliance with R806.2. Provide appropriate upper and lower space vents when applying the reduced area calculation. Account for the existing attic space if removing or blocking existing vents. PLUMBING PLANS: 1. Show a pressure and temperature relief valve at the water heater, P2803.6.1. 2. Provide water hammer arresters wherever quick-closing valves are installed in a water distribution system. Water hammer arresters are required for clothes washer water connections, P2903.5. 3. Provide a revised fixture unit schedule using 2006 code values, P2903.6. Those shown are not consistent with current codes. Include hose bibbs. 4. Provide the BTU demand of each appliance and provide appropriate pipe sizes. A system with total developed length of 133' may require a 1-1/4" pipe between the water heater and stove branch tee and a 1" pipe for the furnace branch. G2413.3 & Table G2413.4(1). MECHANICAL PLANS: 1. Show supply and return ducts with minimum R-8 insulation (includes vented attics) except when completely located inside the thermal envelope, R1103.2.1. 2. Show dryer vent size and location for venting to exterior, M1501. 3. Show an existing or proposed exhaust fan in the existing bathroom with minimum 50 CFM rating R303.3 and M1507.3. 4. Show Utility Room interior combustion air space of 50 CU FT for each 1,000 BTU, M2407.5.1. This requires a door or wall vent opening to the Great Room. Or, show two 100 SQ IN openings, one within 12" of ceiling and the other 12" of floor through the exterior wall, G2407.5.3.1. ELECTRICAL PLANS: 1. Interior alterations require the installation of smoke alarms at existing bedrooms, R313.2.1. Provide notation if existing or proposed. 2. Provide a panel schedule showing wire size of each circuit or notate the wire size for each protection rating, E3602.2. 3. Revise the electrical load calculations following Table E3502.2 for sizing 100% of the dwelling load. Add the total nameplate for the air conditioning unit to the 65.8A sub-total. 4. Provide a branch circuit for the Heat Pump sufficient for serving the load, E3602.11. 5. Show receptacle outlets with no point along the wall line more than 24" from a receptacle outlet, E3801.4.1. Also, show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets, E3603.2 and E3801.3. 6. Show a GFCI receptacle outlet on the same level within 25' of exterior Gas Pack equipment, E3801.11. 7. Indicate the location of the air handling equipment disconnect switch, E4001.5. If you have any questions please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |