Permit Number: T11CM00866
Parcel: 12504112A

Address:
2010 E 1ST ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM00866
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/28/2011 GERRY KOZIOL WWM REVIEW Approved
04/29/2011 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 5-01-11
Activity: T11CM00866
Address: 2010 E. 1st St
Applicant: Metro Permit Express

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Any architect and/or engineer involved in the design of the structure shall seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.
2. Show stairs in garage to storage unit/water heater enclosure.
3. Provide minimum 1-hour fire separation between attached single family residences.
4. As previously requested, provide notation for minimum slope away from foundations, R401.3.
5. As previously requested, clarify section reference to "?" shown on sheet A3 & A3.1. Provide detail for elevation change at garage/house intersection in garage.
6. As previously requested, clarify plumbing code to be used. IRC and UPC plumbing codes are not interchangeable. All notes, schedules, and design must conform to only one of those two codes.
7. As previously requested, two discharges must be provided for washing machine (one to black water and one to gray water building drains).
8. As previously requested, provide make-up air to gas fired dryer. Plan refers to architectural door schedule for louvers but no door schedule is provided.
9. As previously requested, include all minimum loads into electrical load calculation (including laundry and dryer circuits).
10. As previously requested, show receptacle outlets in each bedroom spaced according to E3801.2 (maximum 6 feet from all door openings).
11. As previously requested, provide arc-fault circuit protection on all sleeping room outlets (including smoke detectors).
12. As previously requested, provide cut sheets for all full cut-off lighting fixtures.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review
04/29/2011 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Passed
05/02/2011 JASON GREEN ENGINEERING REVIEW Needs Review
05/02/2011 SREEVES1 ZONING REVIEW Needs Review
05/02/2011 SREEVES1 NPPO REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/02/2011 SUE REEVES OUT TO CUSTOMER Completed