Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM00845
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/12/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A0.00; SHEET INDEX: THERE ARE NO STRUCTURAL SHEETS LISTED IN THE INDEX. PROVIDE. 2. SHEET A0.2.1; PLAN: MOVE THE DIMENSION BETWEEN GRIDS H AND J OUT OF THE BOXED NOTE. 3. SHEET H-1; ELEVATION: PROVIDE A DIMENSION FROM THE WALL TO THE CENTERLINE OF THE VERTICAL GRAB BAR. 4. SHEET H-1; ELEVATION: REVISE THE DIMENSION FROM THE FRONT OF THE WATER CLOSET TO THE CENTERLINE OF THE PAPER DISPENSER PER ICC/ANSI FIGURE 604.7. 5. SHEET H-3; DETAIL 1: REVISE THE DIMENSION FROM THE FRONT OF THE WATER CLOSET TO THE CENTERLINE OF THE PAPER DISPENSER PER ICC/ANSI FIGURE 604.7. 6. SHEET H-3; DETAIL 1: PROVIDE A DIMENSION FROM THE WALL TO THE CENTERLINE OF THE VERTICAL GRAB BAR. 7. SHEET H-3; DETAIL 1: PROVIDE A DIMENSION FOR THE LENGTH OF THE VERTICAL GRAB BAR, AND THE DISTANCE FROM THE FLOOR TO THE BOTTOM OF THE VERTICAL GRAB BAR. 8. SHEET S0.0.0; TABLE 1704.3: DARKEN THE VERBIAGE. 9. SHEET S2.1.0: THERE ARE TWO DETAIL 1'S ON THIS SHEET. REVISE. 10. SHEET S2.1.1: THERE ARE TWO DETAIL 6'S ON THIS SHEET. REVISE. 11. SHEET S2.1.1; DETAIL 12: PROVIDE A DIMENSION INDICATING THE HEIGHT OF THE NEW GROUT IN THE EXISTING CMU WALL. 12. PREVIOUS COMMENT 14: SHEET A4.0.0; DETAIL 4: A DETAIL 11/A4.0.2 IS REFERENCED AT THE BOTTOM OF THE GLASS. THIS DETAIL HAS BEEN OMITTED. CLARIFY. 13. PREVIOUS COMMENT 25: SHEET H-2; HI/LOW DRINKING FOUNTAIN NOTES: THE CITY OF TUCSON STANDARDS REQUIRE THAT ALL LETTERING BE A MINIMUM OF 3/32" IN HEIGHT. 14. PREVIOUS COMMENT 26: SHEET H-2; FIRE LANE AND ENTRY SIGNS: THE CITY OF TUCSON STANDARDS REQUIRE THAT ALL LETTERING BE A MINIMUM OF 3/32" IN HEIGHT. 15. PREVIOUS COMMENT 29: GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 05/20/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM00845 4510 N Oracle Rd Forever 21 Electrical plans denied, new added panel HP is not shown in drawings. Called Mark Brander @ Hallberg Eng., to notify. Ray Majuta, PDSD, C of Tuc, Elect Pln Ck, 2/24/11 Ray.majuta@tucsonaz.gov |
| 05/24/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not resolved; section 2.35 of the mechanical specifications on sheet M901 calls for R-3 insulation on the sheet metal ductwork not located in the conditioned space. : Section 503.2.7, IECC 2006, as amended by the City of Tucson calls for a minimum insulation level of R-4.2 in that case. [Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson.] |
| 05/24/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Install the vacuum relief for the water heater per the manufacturer's listing instructions (i.e. no valves located between the vacuum relief valve and the water heater). Reference: Section 310.4, UPC 2006. [Provide a detail of the water heater installation, including the valves, expansion tank, and vacuum relief. Reference: Sections 103.2.3, 605.5, 608.3, and 608.7 UPC 2006.] |