Permit Number: T11CM00844
Parcel: 107040140

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM00844
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/29/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A3: THE CITY OF TUCSON STANDARDS REQUIRE ALL LETTERING TO BE A MINIMUM OF 3/32" IN HEIGHT. ON THE PLAN, ENLARGE THE DIMENSIONS THAT LOCATE THE RACKS. ON THE PALLET RACK PLAN VIEW, ENLARGE THE VERBIAGE. ON THE PALLET RACK ELEVATION, ENLARGE THE DIMENSIONS.
2. SHEET SCE1 OF 1; GENERAL PROJECT NOTES: NOTE 1 INDICATES THE 2009 IBC REQUIREMENTS WERE USED IN THIS DESIGN. THE CITY OF TUCSON USES THE 2006 IBC. REVISE THE NOTE.
3. SHEET SCE1 OF 1; GENERAL PROJECT NOTES: NOTE 4 INDICATES 1 ANCHOR PER BASE PLATE, BUT DETAIL 1 INDICATES 2. CLARIFY.
4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/11/2011 CINDY AGUILAR OUT TO CUSTOMER Completed
04/11/2011 SUE REEVES REJECT SHELF Completed