Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM00843
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/22/2011 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
03/22/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Clarify the termination of the exhaust fan - does it really stick out 30" outside of the building? 2. Exhaust ducts that are positively-pressurized shall not be located in a return air plenum. 3. Show that the 1300 cfm of exhaust can be compensated with sufficient makeup air to the space. |
03/22/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM00843 1. Water Heater on Mech Plan not in panel schedule. 2. Circuit P1A-27 on plan is part of a 3/pole circuit, and circuit 28 not on power plan. R.T> Majuta PDSD, City of Tucson, Elect PLn Ck 3/22/11 520/837/4988 |
03/22/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
03/22/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
03/22/2011 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
03/22/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Clarify the installation of the sink, P1. In riser diagram A it is shown with a conventional vent and a 2" waste line connecting to a main drain line but details 201 and 205 show two versions of air admittance valves being used. In the plumbing floor plan the 2" waste is connecting to the 2" waste riser for the existing sink - a wet vent? |
03/22/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
03/22/2011 | RONALD BROWN | ADA | REVIEW | Passed | |
03/22/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
04/04/2011 | CAGUILA1 | WWM | REVIEW | Needs Review |