Permit Review Detail
Review Status: Active
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T11CM00814
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/28/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM00814 4351 S Santa Rita Photovoltaic Installation Electrical plans denied for the following: 1. Plans must be legible and clearly distinct, they will be copied , filed, scanned and installed into computer system. Sheet 1 appears to be a copy of a copy, the words and numbers cannot be distingushed. Submittals are required to be legible and min 3/32" text size. 2. All sheets except cover sheet required to be sealed by EE. 3. In addition to one line diagram, a three line diagram is required. 4. Need to show an elevation detail of where the inverter will be, and the existing sub panel will be. 5. If the Weather Station is to be part of this permit ( circuit shown run to it) will need to provide information for it in the form of a specification sheet. If owner is to provide, obtain and submit. R.T. Majuta Elect Pln Ck, PDSD, City of Tucson 3/29/11 Ray.majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/17/2011 | ANY | REJECT SHELF | RECEIVED |