Permit Number: T11CM00812
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM00812
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2011 MICHAEL ST. PAUL ZONING REVIEW Approved
03/17/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide the listing information for the proposed ionizer.
03/17/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM00812

Electrical denied:

1. Track lighting to be figured per 2005 NEC 220.43.B for load calculation.
2. Provide 2006 IECC Budget Lighting Calculations for interior.
3. Receptacle for Ionization unit, will this be installed above cieling,will unit be cord and plug connected ? Nec 2005
400.8.2 does not allow cords above a cieling.
Please clearify items above.

Ray T Majuta,
Elect Pln Ck, PSDS,
City of Tucson,
3/17/11,
Ray.Majuta@tucsonaz.gov
03/17/2011 ROBERT SHERRY WATER REVIEW Approved
03/17/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET C1.0; A1: THE EXISTING TOILET IS NOT ADA COMPLIANT AS STATED. REMOVE NOTE. ACCESSIBLE TOILET IS NOT REQUIRED IN THE STORE, JUST IN THE MALL PER THE 2006 IBC SECTION 2902.4.2.
2. SHEET C1.0; A1: THE BOTTLED WATER COOLER DOES NOT MEET ACCESSIBILITY OR CITY OF TUCSON REQUIREMENTS. IT MUST BE A SINGLE POINT-OF-USE WATER DISPENSER CONNECTED DIRECTLY INTO THE WATER LINE.
03/17/2011 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
03/17/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
03/17/2011 JASON GREEN ENGINEERING REVIEW Approved
03/17/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/17/2011 ERIC NEWCOMB ADA REVIEW Passed
03/24/2011 CAGUILA1 FIRE REVIEW Needs Review