Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM00812
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/17/2011 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 03/17/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide the listing information for the proposed ionizer. |
| 03/17/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM00812 Electrical denied: 1. Track lighting to be figured per 2005 NEC 220.43.B for load calculation. 2. Provide 2006 IECC Budget Lighting Calculations for interior. 3. Receptacle for Ionization unit, will this be installed above cieling,will unit be cord and plug connected ? Nec 2005 400.8.2 does not allow cords above a cieling. Please clearify items above. Ray T Majuta, Elect Pln Ck, PSDS, City of Tucson, 3/17/11, Ray.Majuta@tucsonaz.gov |
| 03/17/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/17/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET C1.0; A1: THE EXISTING TOILET IS NOT ADA COMPLIANT AS STATED. REMOVE NOTE. ACCESSIBLE TOILET IS NOT REQUIRED IN THE STORE, JUST IN THE MALL PER THE 2006 IBC SECTION 2902.4.2. 2. SHEET C1.0; A1: THE BOTTLED WATER COOLER DOES NOT MEET ACCESSIBILITY OR CITY OF TUCSON REQUIREMENTS. IT MUST BE A SINGLE POINT-OF-USE WATER DISPENSER CONNECTED DIRECTLY INTO THE WATER LINE. |
| 03/17/2011 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 03/17/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 03/17/2011 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 03/17/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/17/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 03/24/2011 | CAGUILA1 | FIRE | REVIEW | Needs Review |