Permit Number: T11CM00789
Parcel: 13510150R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM00789
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/03/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The specified instantaneous water heater does not have a microprocessor option. The company does manufacture instantaneous water heaters complete with thermostatic controls but the electrical characteristics are different. (No electrical power has been provided for the water heater per the electrical drawings.)
05/03/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide an exhaust fan for the new restroom per Section 403.3, IMC 2006.
05/17/2011 CPIERCE1 WWM REVIEW Needs Review
05/17/2011 CPIERCE1 BUILDING-COMMERCIAL REVIEW Needs Review
05/17/2011 CPIERCE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review