Review Details: COMMERCIAL - TI
Permit Number - T11CM00789
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/15/2011 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 03/15/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide an exhaust fan for the new restroom per Section 403.3, IMC 2006. |
| 03/15/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | PROVIDE DETAILS FOR NEW PANEL, AND WHERE RELOCATED OUTLETS COME FROM |
| 03/15/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/15/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. WALLS IN THE RESTROOM MUST MEET IBC CRITERIA IN SECTION 1210.2. PROVIDE. 2. DRINKING FOUNTAIN MUST BE PROVIDED (HIGH/LOW OR SINGLE POINT-OF-USE) PER IBC SECTION 2902.1. 3. PROVIDE A DETAIL OF THE GRAB BARS IN THE RESTROOM PER ICC/ANSI A117.1-2003, FIGURE 604.5.1. 4. PROVIDE A DIMENSIONED PLAN OF THE RESTROOM INDICATING WATER CLOSET CLEARANCE MEETS THE ICC/ANSI A117.1-2003 FIGURE 604.3. 5. BRACE THE TOP OF THE NEW INTERIOR WALLS TO MEET IBC SECTION 1607.13. PROVIDE DETAILS SHOWING THE BRACE SIZE AND SPACING, AND THE CONNECTION TO THE STRUCTURE ABOVE AND TO THE TOP OF THE WALL. |
| 03/15/2011 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 03/15/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide a plumbing plan for the relocated restroom. |
| 03/15/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 03/15/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 03/15/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 05/03/2011 | CPIERCE1 | WWM | REVIEW | Needs Review |