Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11CM00789
Parcel: 13510150R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM00789
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/15/2011 STEVE SHIELDS ZONING REVIEW Approved
03/15/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide an exhaust fan for the new restroom per Section 403.3, IMC 2006.
03/15/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied PROVIDE DETAILS FOR NEW PANEL, AND WHERE RELOCATED OUTLETS COME FROM
03/15/2011 ROBERT SHERRY WATER REVIEW Approved
03/15/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. WALLS IN THE RESTROOM MUST MEET IBC CRITERIA IN SECTION 1210.2. PROVIDE.
2. DRINKING FOUNTAIN MUST BE PROVIDED (HIGH/LOW OR SINGLE POINT-OF-USE) PER IBC SECTION 2902.1.
3. PROVIDE A DETAIL OF THE GRAB BARS IN THE RESTROOM PER ICC/ANSI A117.1-2003, FIGURE 604.5.1.
4. PROVIDE A DIMENSIONED PLAN OF THE RESTROOM INDICATING WATER CLOSET CLEARANCE MEETS THE
ICC/ANSI A117.1-2003 FIGURE 604.3.
5. BRACE THE TOP OF THE NEW INTERIOR WALLS TO MEET IBC SECTION 1607.13. PROVIDE DETAILS SHOWING THE BRACE SIZE AND SPACING, AND THE CONNECTION TO THE STRUCTURE ABOVE AND TO THE TOP OF THE WALL.
03/15/2011 LOREN MAKUS ENGINEERING REVIEW Approved
03/15/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide a plumbing plan for the relocated restroom.
03/15/2011 DAVE MANN FIRE REVIEW Approved
03/15/2011 ERIC NEWCOMB ADA REVIEW Passed
03/15/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/03/2011 CPIERCE1 WWM REVIEW Needs Review