Permit Number: T11CM00788
Parcel: 11615077H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM00788
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/15/2011 STEVE SHIELDS ZONING REVIEW Approved
03/15/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
03/15/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied SHOW WHERE CKTS ARE TIED IN, WHETHER THEY ARE NEW HOMERUNS, PANEL SCHEDULE, LOAD CALCS.
03/15/2011 ROBERT SHERRY WATER REVIEW Approved
03/15/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE A HIGH/LOW OR SINGLE POINT-OF-USE DRINKING FOUNTAIN AND A SERVICE SINK PER 2006 IBC TABLE 2902.1.
03/15/2011 LOREN MAKUS ENGINEERING REVIEW Approved
03/15/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a drinking fountain.
2. Verify that the breakroom sink qualifies as a service sink (i.e.2" trap)
03/15/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/15/2011 ERIC NEWCOMB ADA REVIEW Passed
04/20/2011 CPIERCE1 WWM REVIEW Needs Review
04/20/2011 CPIERCE1 FIRE REVIEW Needs Review