Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM00788
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/15/2011 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 03/15/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 03/15/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | SHOW WHERE CKTS ARE TIED IN, WHETHER THEY ARE NEW HOMERUNS, PANEL SCHEDULE, LOAD CALCS. |
| 03/15/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/15/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PROVIDE A HIGH/LOW OR SINGLE POINT-OF-USE DRINKING FOUNTAIN AND A SERVICE SINK PER 2006 IBC TABLE 2902.1. |
| 03/15/2011 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 03/15/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a drinking fountain. 2. Verify that the breakroom sink qualifies as a service sink (i.e.2" trap) |
| 03/15/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/15/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 04/20/2011 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 04/20/2011 | CPIERCE1 | FIRE | REVIEW | Needs Review |