Permit Number: T11CM00753
Parcel: 11706097C

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T11CM00753
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2011 DAVE MANN FIRE REVIEW Approved
03/17/2011 RONALD BROWN ADA REVIEW Denied 1. Please provide one site plan (key plan) showing all the modifications plus all the existing adjacent buildings and complete pedestrian connections to these building from the new modifications.
a. Sheet A1.2: Show the East end of the marked crossing connection complete to the existing building including all required ramps, accessible routes, detectable warnings and etc.
b. Sheet A1.1: Show the accessible route connection to the recycle enclosure.
c. A blow up of detail 2/A1.0 without all the staging and phasing poche' would be nice.
SHEET A1.1
2. Zom=ning will probably require a pedestrian route to the recycle enclosure. Reference Zoning comments.
SHEET A1.2
3. Please complete the marked crossing hump. Show all existing conditiions and required modifications. Also, at detail 2/5.2.
SHEET A1.3
4. Please complete the marked crossing to the MLK building. Show all existing conditiions and required modifications.
END OF REVIEW
03/22/2011 GERRY KOZIOL WWM REVIEW Passed
03/25/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approv-Cond Need to provide special inspection certifications for review and approval prior to permit issuance
03/29/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Show how the water fountain/bottle filler is to be installed (e.g. foundation, valves, and drain provisions). Reference: Section 103.2.3, UPC 2006.
03/29/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
03/29/2011 ROBERT SHERRY WATER REVIEW Denied 1. Show the required size of the water meter (or water meters if the irrigation water is to have a separate meter).
2. Show the required size of the backflow preventers for the domestic water service and for the irrigation water meter.
04/04/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM00753
215 E Congress
Bus Shelter

1. The fixture type not listed on plan for East side row of fixtures.
2. Fixture type D on plan shown going to existing HV-8
and 17 (277/480v), appear on the discription to indicate 120v ?

Ray Majuta,
PDSD, C of Tuc,
Elect Pln Ck,
4/5/11
520/837/4988
04/06/2011 TERRY STEVENS ZONING REVIEW Approved
04/06/2011 LOREN MAKUS ENGINEERING REVIEW Approved