Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T11CM00753
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/14/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
03/17/2011 | RONALD BROWN | ADA | REVIEW | Denied | 1. Please provide one site plan (key plan) showing all the modifications plus all the existing adjacent buildings and complete pedestrian connections to these building from the new modifications. a. Sheet A1.2: Show the East end of the marked crossing connection complete to the existing building including all required ramps, accessible routes, detectable warnings and etc. b. Sheet A1.1: Show the accessible route connection to the recycle enclosure. c. A blow up of detail 2/A1.0 without all the staging and phasing poche' would be nice. SHEET A1.1 2. Zom=ning will probably require a pedestrian route to the recycle enclosure. Reference Zoning comments. SHEET A1.2 3. Please complete the marked crossing hump. Show all existing conditiions and required modifications. Also, at detail 2/5.2. SHEET A1.3 4. Please complete the marked crossing to the MLK building. Show all existing conditiions and required modifications. END OF REVIEW |
03/22/2011 | GERRY KOZIOL | WWM | REVIEW | Passed | |
03/25/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approv-Cond | Need to provide special inspection certifications for review and approval prior to permit issuance |
03/29/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Show how the water fountain/bottle filler is to be installed (e.g. foundation, valves, and drain provisions). Reference: Section 103.2.3, UPC 2006. |
03/29/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
03/29/2011 | ROBERT SHERRY | WATER | REVIEW | Denied | 1. Show the required size of the water meter (or water meters if the irrigation water is to have a separate meter). 2. Show the required size of the backflow preventers for the domestic water service and for the irrigation water meter. |
04/04/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM00753 215 E Congress Bus Shelter 1. The fixture type not listed on plan for East side row of fixtures. 2. Fixture type D on plan shown going to existing HV-8 and 17 (277/480v), appear on the discription to indicate 120v ? Ray Majuta, PDSD, C of Tuc, Elect Pln Ck, 4/5/11 520/837/4988 |
04/06/2011 | TERRY STEVENS | ZONING | REVIEW | Approved | |
04/06/2011 | LOREN MAKUS | ENGINEERING | REVIEW | Approved |