Permit Number - T11CM00746
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/14/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 03/16/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the Kitchen Equipment Schedule to show an indirect waste connection for the new prep sink (item 10). Reference: Section 801.2, UPC 2006. 2. Detail B/P.1 shows two 3-compartment sinks (P-3); should one of them be a prep sink? Reference: Section 103.2.3, UPC 2006. 3. Clarify the installation of the instantaneous water heater; provide manufacturer's listing information. Reference: Section 103.2.3, UPC 2006. 4. Clarify the sizes of the gas pipes and remove the contradictory information (e.g. pipe sizes and developed lengths) shown on the water heater schematic and the gas piping schematic. Reference: Section 103.2.3, UPC 2006. |
| 03/16/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Verify the suitability of re-using the existing flue with the new instantaneous water heater. Reference: Sections 310.4 and 510.1, UPC 2006. |