Permit Number: T11CM00746
Parcel: 12308070B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM00746
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2011 GERRY KOZIOL WWM REVIEW Approved
03/16/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the Kitchen Equipment Schedule to show an indirect waste connection for the new prep sink (item 10). Reference: Section 801.2, UPC 2006.
2. Detail B/P.1 shows two 3-compartment sinks (P-3); should one of them be a prep sink? Reference: Section 103.2.3, UPC 2006.
3. Clarify the installation of the instantaneous water heater; provide manufacturer's listing information. Reference: Section 103.2.3, UPC 2006.
4. Clarify the sizes of the gas pipes and remove the contradictory information (e.g. pipe sizes and developed lengths) shown on the water heater schematic and the gas piping schematic. Reference: Section 103.2.3, UPC 2006.
03/16/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Verify the suitability of re-using the existing flue with the new instantaneous water heater. Reference: Sections 310.4 and 510.1, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/22/2011 GERARDO BONILLA OUT TO CUSTOMER Completed
03/22/2011 SUE REEVES REJECT SHELF Completed