Permit Number: T11CM00692
Parcel: 10512020C

Address:
4128 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM00692
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2011 STEVE SHIELDS ZONING REVIEW Approved
03/07/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/07/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T11CM00692
4128 N Oracle Rd

Electrical loads for track lighting per 2005 NEC 220-43 B requires 150 va for every 2'. The loading for this lighting must be determined befor the load can be sized and the IECC Budget calculation can be deterimed . Please provide even though the owner is to provide.


Ray T Majuta,
Elect PLn Ck,
PDSD, City of Tucson,
3/7/11,
Ray.Majuta@tucsonaz.gov
03/07/2011 ROBERT SHERRY WATER REVIEW Approved
03/07/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/07/2011 JASON GREEN ENGINEERING REVIEW Approved
03/07/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
03/07/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/07/2011 ERIC NEWCOMB ADA REVIEW Passed
03/14/2011 GERRY KOZIOL WWM REVIEW Approved
03/14/2011 CPIERCE1 FIRE REVIEW Needs Review