Permit Number: T11CM00670
Parcel: 123111840

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM00670
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/21/2013 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
Show corrections and revisions on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and notate sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

GENERAL NOTES:

1. Limit all code references to those recognized by the City of Tucson. Adopted codes are listed at the Planning & Development Services web site. Update the NEC code referenced on sheet A-1.2 to 2011 NEC.
2. Provide keynote references at the Guest Bathroom, sheet A-3.

FLOOR PLANS:

1. Show the door from a garage to dwelling with a 20-minute fire rating (or 1-3/8" solid core) with self-closing and self-latching provision, 2006 IRC Amendment section 309.1. Update Door Schedule #17 sheet A-1.2.

PLUMBING PLANS:

1. Clarify the water heater notation on sheet P-1 as 20 gallon storage or on-demand, G2413.3.

ELECTRICAL PLANS:

1. Provide a panel schedule showing wire size of each circuit or notate the wire size for each protection rating, E3602.2.
2. Show all receptacle outlets within 6' of a sink with ground fault circuit interrupting protection, E3802. Include the Laundry Room sink.

OUTDOOR LIGHTING CODE

1. Show compliance with City of Tucson Outdoor Lighting Code; the total property lighting limit for area E3 is 55,000 lumens per acre (9,460 lumens) and the unshielded limit for area E3 is 12,000 lumens per acre (2,064 lumens). Identify one or more fixture types as full cut-off. Currently, the plans do not show compliance for the unshielded (non-shielded) limit, sheet #A-1.2.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/26/2013 AROMERO4 OUT TO CUSTOMER Completed
06/26/2013 CPIERCE1 REJECT SHELF Completed