Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T11CM00662
Parcel: 10609043B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM00662
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/04/2011 MARTIN BROWN FIRE REVIEW Approved
03/14/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET g1.2; CODE ANALYSIS: PROVIDE VERBIAGE IN THE ANALYSIS INDICATING ADEQUACY OF THE EXISTING PLUMBING FIXTURES FOR THE 70 ADDITIONAL OCCUPANTS, AND THAT THE LOCATION OF THE TOILET FACILITIES MEET THE REQUIREMENTS OF SECTION 2902.4.1 OF THE 2006 IBC.
2. SHEET s2.0 (COLUMN SCHEDULE); STRUCTURAL CALCULATIONS: DID NOT LOCATE THE STEEL COLUMN C1 DESIGN IN THE CALCULATIONS. VERIFY.
3. SHEET s2.0 (FOOTING SCHEDULE); STRUCTURAL CALCULATIONS: DID NOT LOCATE THE FOOTING F2 DESIGN IN THE CALCULATIONS. VERIFY.
4. SHEET s2.0 (LEDGER SCHEDULE); STRUCTURAL CALCULATIONS: DID NOT LOCATE THE STEEL LEDGER DESIGN IN THE CALCULATIONS. VERIFY.
5. SHEET s2.0 (FOUNDATION PLAN); DETAIL 111: A NOTE 3 ON THE FOUNDATION PLAN INDICATES JOINT FILLER AT THE EXISTING BUILDING, WHILE DETAIL 111 DOES NOT INDICATE THE FILLER. VERIFY.
6. SHEET s4.0 (DETAIL 208); SHEET 1a5.1 (DETAIL 11): THE LOCATION OF THE TS6X2 THAT RUNS PARALLEL TO THE WALL VARIES ON THESE TWO DETAILS. COORDINATE.
7. SHEET 1a5.4; DETAIL 2: IS THERE A SITE WALL ON THIS PROJECT AS DETAILED HERE? NO FEE WAS INCLUDED FOR THIS. VERIFY.
8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/16/2011 GERRY KOZIOL WWM REVIEW Passed
03/24/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the size of the scupper for the 1460-square foot portion of the addition to comply with the requirements of Section 1101.11.2.1, UPC 2006. Refer also to Section 1106.4, UPC 2006.
03/24/2011 ROBERT SHERRY WATER REVIEW Approved
03/24/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the energy code analysis, coordinating the building components used in the analysis with those shown on the drawing. Specifically, the roof construction in the report is shown as "other" but no supporting documentation has been provided (see footnote 'b' on the submitted COMcheck Envelope Compliance Certificate). Reference: Section 502, IECC 2006, as amended by the City of Tucson.
03/31/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/05/2011 CPIERCE1 OUT TO CUSTOMER Completed
04/05/2011 SUE REEVES REJECT SHELF Completed