Permit Number: T11CM00660
Parcel: 140122160

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM00660
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/04/2011 MARTIN BROWN FIRE REVIEW Approved
03/04/2011 GERRY KOZIOL WWM REVIEW Approved
03/09/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEET A8.1
1. Generic details are not acceptable. Please delete all code copied details shown on sheets ADA 1.0 and A1.1 and show all accessible dimensions, accessories and requirements on the actual design toilet floor plan and elevations.
SHEETS ADA1.0 AND 1.1
2. Please delete all details shown on these two sheets that are not relative to the design of this project.
3. Detail 12/ADA1.1: As per COT DOT standards, the bottom of the main sign is to be 7' a.f.g.
4. Existing building background on all floor plans are drafted too light. Please increase the line weight for the existinmg conditions for all floor plans and resubmit.
END OF REVIEW
03/09/2011 JASON GREEN ENGINEERING REVIEW Approved
03/10/2011 STEVE SHIELDS ZONING REVIEW Approved
03/23/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Verify that the two restrooms have adequate ventilation. Reference: Section 403.3, IMC 2006.
03/23/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide complete plumbing plans for the new work, including waste and vent isometrics of the new work. Reference: Section 103.2.3, UPC 2006.
03/23/2011 ROBERT SHERRY WATER REVIEW Approved
03/24/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM00660
4951 S Campbell

Elecrtrical plans denied for the following:
1. All lettering and numbering to be min 3/32''.
2. Provide a panel schedule with loads , location ,
identify circuits on power and lighting plans
3. Provide the date ( when to when ), that information obtained for Load Comsumption Report.
4. Single line diagram too light, too small, these sheets need to be copied, recorded, and transfered to computer.

Ray T Majuta,
Elect Plan Ck,
PDSD, City Of Tucson,
3/28/11,
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
06/21/2011 SUE REEVES OUT TO CUSTOMER Completed
06/21/2011 SUE REEVES REJECT SHELF Completed