Permit Number: T11CM00658
Parcel: 130144450

Address:
3930 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM00658
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/04/2011 MARTIN BROWN FIRE REVIEW Approved
03/04/2011 GERRY KOZIOL WWM REVIEW Approved
03/09/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. This project is governed by the 2006 IBC which has as the ICC (ANSI 117.1 2003 Edition) as the compliant accessibility code.
a. Please change all details and references from ADA to ICC (ANSI 117.1, 2003 Edition).
b. Please review all accessibility design details and change them to be in compliance with the ICC (ANSI 117.1, 2003 Edition).
c. An accessible compliant review for ADA Accessible Standards may be conducted upon an approved appeal to the building official, Mr. Ron Boose. If so desired, please complete a building official appeal and submit for review and approval. A fee of $132.00 is required for processing.
2. Generic details are not acceptable. Sheet nos. ADA1.0 and ADA 1.1 are mostly code copied details that that no relevance to the actual design of the accessibility elements of this project.
a. Please delete all details not relevant to this project.
b. Please provide all accessible requirements (dimensions and accessories) on the actual toilet design elevations and floor plan.
3. Please include the vertical grad bar in all required toilet elevations: A/A8.2, 1, 2, 6, and 7/A8.2.
4. Existing building background on all floor plans are drafted too light. Please increase the line weight for the existinmg conditions for all floor plans and resubmit.
END OF REVIEW
03/09/2011 JASON GREEN ENGINEERING REVIEW Approved
03/10/2011 STEVE SHIELDS ZONING REVIEW Approved
03/23/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/23/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide complete plumbing plans for the new work, including waste and vent isometrics of the new work. Reference: Section 103.2.3, UPC 2006.
03/23/2011 ROBERT SHERRY WATER REVIEW Approved
03/24/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM00658
3930 E 22nd St

Electrical plans denied for the following:

1. Review all lettering and numbering , min 3/32"
2. Identify circuits on power and lighting plans.
3. Show location of Pnl B.
4. Date Load Calculation Report.

Ray T Majuta
PDSD, City of Tucson
Elect Pln CK
3/28/11
Ray.majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
06/21/2011 SUE REEVES OUT TO CUSTOMER Completed
06/21/2011 SUE REEVES REJECT SHELF Completed