Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM00657
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/04/2011 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/04/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 03/07/2011 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 03/09/2011 | STEVE SHIELDS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Taco Bell - 3455 E. Grant Road T11CM00657 Building Plan (1st Review) TRANSMITTAL DATE: March 9, 2011 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Zoning can not approve the building plan until the site plan has been approved. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 C:\planning\grading\t11cm00657.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: |
| 03/15/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | SHEET A8.1 1. The clear dimension width for the women's accessible toilet stall must be 5' wide as per ICC (ANSI 117.1), Section 604.8.2. 2. Generic details are not acceptable. Please delete all code copied details shown on sheets ADA 1.0 and A1.1 and show all accessible dimensions, accessories and requirements on the actual design toilet floor plan and elevations. SHEETS ADA1.0 AND 1.1 3. Please delete all details shown on these two sheets that are not relative to the design of this project. 4. Detail 12/ADA1.1: As per COT DOT standards, the bottom of the main sign is to be 7' a.f.g. 5. Existing building background on all floor plans are drafted too light. Please increase the line weight for the existinmg conditions for all floor plans and resubmit. END OF REVIEW |
| 03/23/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 03/23/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide complete plumbing plans for the new work, including waste and vent isometrics of the new work. Reference: Section 103.2.3, UPC 2006. 2. Show how the temperature of the hot water supply to the relocated public lavatory is to be controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. |
| 03/23/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/24/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM00657 3455 E Grtant Electrical plans denied for the following: 1. All lettering and numbering to be min 3/32". 2. Date Load Comsumption Report, must date time of recording. 3. Panel B too light, also provide it's location. 4. Provide circuit identification on power and lighting plans. Ray T Majuta, Elect Pln Ck, PDSD, City of Tucson, 3/28/11 Ray.majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/25/2011 | SUE REEVES | OUT TO CUSTOMER | Completed |
| 07/25/2011 | SUE REEVES | REJECT SHELF | Completed |