Permit Number: T11CM00651
Parcel: 14025040H

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T11CM00651
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/03/2011 GERRY KOZIOL WWM REVIEW Approved
03/28/2011 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 3-30-11
Activity: T11CM00651
Address: 5823 S Randall Blvd
Applicant: Dolores Cardenas

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

STRUCTURAL / FRAMING PLAN:
1. Justify rafter size and spacing for front porch design R801.2.
2. Justify 4x12 beams for their intended spans and roof loading R801.2
3. Show footings minimum 12" below grade R319.1.

PLUMBING PLAN:
4. Verify total developed length of water supply piping from the water meter to the furthest plumbing fixture served P2903.7.
5. Size gas supply piping according to proposed demand G2413.1.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/12/2011 GERARDO BONILLA OUT TO CUSTOMER Completed
04/12/2011 SUE REEVES REJECT SHELF Completed