Permit Number: T11CM00643
Parcel: 13317064C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM00643
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/12/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PER PREVIOUS COMMENTS 1, 2, 3, AND 4, SHEET A3 WAS NOT REVISED. VERIFY.
04/12/2011 GERRY KOZIOL WWM REVIEW Denied need wastewater plumbing demo drawings for this suite to match demo list prior to requesting wastewater credit from 5th floor
04/14/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/14/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not resolved. The indirect waste receptor shall not be installed in an unventilated space; see Section 802.3, IPC 2006. [Clarify the locations of the FS-1 indirect waste receptors: they appear to be located within inaccessible, unventilated spaces. Reference: Section 802.3, IPC 2006.]
04/22/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved