Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM00643
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/12/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PER PREVIOUS COMMENTS 1, 2, 3, AND 4, SHEET A3 WAS NOT REVISED. VERIFY. |
04/12/2011 | GERRY KOZIOL | WWM | REVIEW | Denied | need wastewater plumbing demo drawings for this suite to match demo list prior to requesting wastewater credit from 5th floor |
04/14/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
04/14/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Comment not resolved. The indirect waste receptor shall not be installed in an unventilated space; see Section 802.3, IPC 2006. [Clarify the locations of the FS-1 indirect waste receptors: they appear to be located within inaccessible, unventilated spaces. Reference: Section 802.3, IPC 2006.] |
04/22/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved |