Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T11CM00643
Parcel: 13317064C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM00643
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/08/2011 DAVE MANN FIRE REVIEW Approved
03/10/2011 JASON GREEN ENGINEERING REVIEW Approved
03/16/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEETS A1.1/A1.2/A3/A5/A5.1; KEY NOTE 8.2: IS THE REFERENCE TO 2/A1 CORRECT? VERIFY.
2. SHEETS A1.1/A1.2/A3/A5/A5.1; KEY NOTE 8.4: IS THE REFERENCE TO 16/A5 CORRECT? VERIFY.
3. SHEETS A1.1/A1.2/A3/A5/A5.1; KEY NOTE 10.1: THIS PROJECT DOES NOT USE THE ADA ACCESSIBILITY GUIDELINES. REVISE THE REFERENCE TO THE ICC/ANSI A117.1-2003.
4. SHEETS A1.1/A1.2/A3/A5/A5.1; KEY NOTES 10.6/10.7/10.8: IS THE REFERENCE TO 1/A6 CORRECT? VERIFY.
5. SHEET A5; ELEVATIONS 5/6/7: DRINKING FOUNTAINS ARE REQUIRED TO BE HIGH/LOW OR SINGLE POINT-OF-USE DISPENSERS. REVISE.
6. SHEET A5; ELEVATIONS 2/3/4: THE VERTICAL GRAB BAR SHOULD BE LOCATED FROM THE BACK WALL. REVISE.
7. SHEET A5; ELEVATION 3C: PROVIDE DIMENSIONED ELEVATIONS FOR THE GRAB BARS IN THE SHOWER PER ICC/ANSI A117.1-2003, SECTION 608.
8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/22/2011 GERRY KOZIOL WWM REVIEW Denied need wastewater plumbing demo drawings for this suite to match demo list prior to requesting wastewater credit from 5th floor
03/25/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the plumbing floor plans with the waste & vent and water riser diagrams (e.g. the detail tags on the plumbing plans refer to plumbing pages that are not in the drawing set and P-9 refers to both a drinking fountain and an existing sink). Reference: Section 106.3.1, IPC 2006.
2. Clarify the installation of P9 and P8 as shown in riser diagrams 3/P2.1 and 4/P2.1: is the ice maker hook-up directly above the drinking fountain and where is the drain for the drinking fountain. The architectural floor plans indicate that a point-of-use water dispenser is located where you show a dual-height water fountain (P8) located. Reference: Section 106.3.1, IPC 2006.
3. Clarify the locations of the FS-1 indirect waste receptors: they appear to be located within inaccessible, unventilated spaces. Reference: Section 802.3, IPC 2006.
03/25/2011 ROBERT SHERRY WATER REVIEW Approved
03/25/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify note 4 in the air device schedule; only the top third of the lettering is visible. Reference: Section 106.3.1, IMC 2006.
2. Clarify how compliance with Section 307.2.3 IMC 2006 (e.g.. provide auxiliary drain pans or secondary drain systems for fan coil units) has been obtained.
3. Positively pressurized exhaust ducts may not pass through a plenum. Reference: Section 601.4, IMC 2006.
04/01/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM00643
6561 E Carondelet Dr
Medical TI

The electrical plans have been denied for the following:

1. Sheet E-7.1, the panel names on this sheet did not print.
2. Sheet E-7.1, Panel NL-1 has a 30/3 CB feeding a 60 Amp fused disconnect.
3. Sheet E-6.1, correct the name to circuits 1,3,5, Panel B to indicate Panel A without SRV.
4. Provide a total load calculation showing new load this project plus existing.

Ray T Majuta,
PDSD, C of Tuc.,
Elect Pln Ck,
4/3/11
Ray.majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
04/05/2011 CPIERCE1 OUT TO CUSTOMER Completed
04/05/2011 SUE REEVES REJECT SHELF Completed