Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11CM00630
Parcel: 128102940

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM00630
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM00630,
5441 E Williams Ci # 200,
75.9 KW Photovoltaic System,


The Electrical Plans require the following information in order to issue permit:

1. Provide a specification sheet of the modules.
2. Provide a specification sheet of the 13 and 15 KW Inverters.
3. The electrical sheets are to include an elevation drawing showing the wall on which the Main AC Combiner Panel and the Inverters ar to be installed on, currently a top view of this is provided on Sheet L-1.2 and front view on L-1.4, these are not covered under the EE's stamp. The electrical drawings do not indicate where the Main PV Disconnect and PV Meter will be installed, would they be required to be NEMA 3R ?
4. The General Notes on Sheet L-1.4 , I presume , are provided by the Solar Energy Group, and may be a general set of requirements they include on their plans, the elevation detail of the Inverters and AC Combination Panel are also included, to prevent confusion at installation on site for the installer and inspector, these should be combined with the notes provided by the EE on the electrical sheets,or make reference to this on the plan.

Ray T Majuta,
Elect Pln CK,PDSD,
City of Tucson,
3/8/11,
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
03/09/2011 GERARDO BONILLA OUT TO CUSTOMER Completed
03/09/2011 SUE REEVES REJECT SHELF Completed