Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T11CM00616
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/06/2011 | DAVE MANN | FIRE | REVIEW | Denied | Notes on A1.02G indicate no sprinklers are provided on upper floors. The fire pump room must be sprinklered. Dumpsters (if DSMR is approved for inside) must be in sprinklered portions of the building. No floor drain was shown on the plumbing. |
04/12/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not resolved. The manifold design contains size reductions (Section 1101.5), fittings and connections that are not approved for drainage (Section 1101.6), and the presence of "ledges, shoulders, or reductions capable of retarding or obstructing flow in the piping" (Section 1102.7). [Sheet P-2.1 shows two storm water manifolds. Explain how these assemblies comply with the requirements of Sections 1101.5, 1101.6, and 1102.7, IPC 2006.] 2. Provide a cleanout at the base of waste stack P1 and at the upper terminal of the horizontal waste lines P2, P3, P4, and P5. Reference: Sections 708.3.1 and 708.3.4, IPC 2006. (Note: the continuation of these horizontal waste lines are not yet shown on the building plans.) |
04/12/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
04/12/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approv-Cond | 1. Special Inspection Certifications will be required to be reviewed and approved prior to permit issue. 2. An approved site plan shall be submitted prior to permit issuance. |
04/18/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM00606 550 N 5th AV Parking Garage Electrical plans denied for following: 1. Item #2 from last reviiew, "provide specification sheets for Fire Pump, Jockey Pump and Controllers," your response "not available at this time". I will require these in order to approve this permit. 2. Item # 8 last review," provide 2006 IECC Budget Lighting Caculations:, your response,"provided ", I could not find these with resubmittal or on plans. Ray Majuta, Elect Plan Review, PDSD, City of Tucson, 4/18/11 Ray.majuta@tucsonaz.gov |
04/19/2011 | LAITH ALSHAMI | ENGINEERING | REVIEW | Denied | Laith Alshami, Engineering and Floodplain Review, 04/19/2011, Submit copies of the approved Development Package for review and approval. |
04/20/2011 | DAVID RIVERA | ZONING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/27/2011 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
04/27/2011 | SUE REEVES | REJECT SHELF | Completed |