Permit Number: T11CM00616
Parcel: 117043440

Address:
550 N 5TH AV 10

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T11CM00616
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/06/2011 DAVE MANN FIRE REVIEW Denied Notes on A1.02G indicate no sprinklers are provided on upper floors. The fire pump room must be sprinklered.
Dumpsters (if DSMR is approved for inside) must be in sprinklered portions of the building.

No floor drain was shown on the plumbing.
04/12/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not resolved. The manifold design contains size reductions (Section 1101.5), fittings and connections that are not approved for drainage (Section 1101.6), and the presence of "ledges, shoulders, or reductions capable of retarding or obstructing flow in the piping" (Section 1102.7). [Sheet P-2.1 shows two storm water manifolds. Explain how these assemblies comply with the requirements of Sections 1101.5, 1101.6, and 1102.7, IPC 2006.]
2. Provide a cleanout at the base of waste stack P1 and at the upper terminal of the horizontal waste lines P2, P3, P4, and P5. Reference: Sections 708.3.1 and 708.3.4, IPC 2006. (Note: the continuation of these horizontal waste lines are not yet shown on the building plans.)
04/12/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/12/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approv-Cond 1. Special Inspection Certifications will be required to be reviewed and approved prior to permit issue.
2. An approved site plan shall be submitted prior to permit issuance.
04/18/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM00606
550 N 5th AV
Parking Garage


Electrical plans denied for following:

1. Item #2 from last reviiew, "provide specification sheets for Fire Pump, Jockey Pump and Controllers," your response "not available at this time". I will require these in order to approve this permit.
2. Item # 8 last review," provide 2006 IECC Budget Lighting Caculations:, your response,"provided ", I could not find these with resubmittal or on plans.


Ray Majuta,
Elect Plan Review,
PDSD, City of Tucson,
4/18/11
Ray.majuta@tucsonaz.gov
04/19/2011 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Engineering and Floodplain Review, 04/19/2011,

Submit copies of the approved Development Package for review and approval.
04/20/2011 DAVID RIVERA ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/27/2011 GERARDO BONILLA OUT TO CUSTOMER Completed
04/27/2011 SUE REEVES REJECT SHELF Completed