Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T11CM00604
Parcel: 129041820

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM00604
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/26/2011 MARTIN BROWN FIRE REVIEW Denied Fire Comments:

The fire wall for the property line must continue through the overhang. See IFC Chapter 7 and IBC 705.

The overhang on the east side cannot extend closer than 10 feet from the building at 2012. See IBC 705.
04/26/2011 MARTIN BROWN FIRE REVIEW Denied The plans have a new note but still show a mixture of steel and wood framing and no type x gyp board.
05/06/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied 1. Is the fixture type a Full cut Off, or a partially sheilded type.Provide a spec sheet.
2. Where will the receptacles get there power from , what circuits are to be used.

Ray Majuta,
PDSD, City of Tuc,
Elect Pln Ck
5/6/11
05/06/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied In order to properly review the three connected structures for code compliance pertaining ro fire separations and overhangs (reference Fire comments), please provide a site plan showing all connected properties and their physical relationship to each other and site parking and drive entrances and property lines.
05/17/2011 CPIERCE1 ZONING REVIEW Needs Review