04/26/2011 MARTIN BROWN FIRE REVIEW Denied Fire Comments:

The fire wall for the property line must continue through the overhang. See IFC Chapter 7 and IBC 705.

The overhang on the east side cannot extend closer than 10 feet from the building at 2012. See IBC 705.
04/26/2011 MARTIN BROWN FIRE REVIEW Denied The plans have a new note but still show a mixture of steel and wood framing and no type x gyp board.
05/06/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied 1. Is the fixture type a Full cut Off, or a partially sheilded type.Provide a spec sheet.
2. Where will the receptacles get there power from , what circuits are to be used.

Ray Majuta,
PDSD, City of Tuc,
Elect Pln Ck
5/6/11
05/06/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied In order to properly review the three connected structures for code compliance pertaining ro fire separations and overhangs (reference Fire comments), please provide a site plan showing all connected properties and their physical relationship to each other and site parking and drive entrances and property lines.
05/17/2011 CPIERCE1 ZONING REVIEW Needs Review