Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM00604
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/26/2011 | MARTIN BROWN | FIRE | REVIEW | Denied | Fire Comments: The fire wall for the property line must continue through the overhang. See IFC Chapter 7 and IBC 705. The overhang on the east side cannot extend closer than 10 feet from the building at 2012. See IBC 705. |
04/26/2011 | MARTIN BROWN | FIRE | REVIEW | Denied | The plans have a new note but still show a mixture of steel and wood framing and no type x gyp board. |
05/06/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1. Is the fixture type a Full cut Off, or a partially sheilded type.Provide a spec sheet. 2. Where will the receptacles get there power from , what circuits are to be used. Ray Majuta, PDSD, City of Tuc, Elect Pln Ck 5/6/11 |
05/06/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | In order to properly review the three connected structures for code compliance pertaining ro fire separations and overhangs (reference Fire comments), please provide a site plan showing all connected properties and their physical relationship to each other and site parking and drive entrances and property lines. |
05/17/2011 | CPIERCE1 | ZONING | REVIEW | Needs Review |