Permit Number: T11CM00603
Parcel: 129041830

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM00603
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/26/2011 MARTIN BROWN FIRE REVIEW Denied Fire Comments:

The fire wall for the property line must continue through the overhang. See IFC Chapter 7 and IBC 705.
04/26/2011 MARTIN BROWN FIRE REVIEW Denied The plans have a new note but still show a mixture of steel and wood framing and no type x gyp board.
05/06/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied In order to properly review the three connected structures for code compliance pertaining ro fire separations and overhangs (reference Fire comments), please provide a site plan showing all connected properties and their physical relationship to each other and site parking and drive entrances and property lines.
05/06/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied 1. Fixture F1 is a recessed type, F1A is also a recessed type mounted in portal ? Plan shows mounting on outside of building wall.
2. Where will the sign receptacles get power from ?, List circuits to be used.

Ray T Majuta
PDSD City of Tucson
Elect Plan Ck
5/6/11
05/17/2011 CPIERCE1 ZONING REVIEW Needs Review