Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Active
Review Details: MODULAR BUILDINGS
Permit Number - T11CM00592
Review Name: MODULAR BUILDINGS
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/18/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | See State of Arizona for placement permit |
| 05/18/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/18/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 05/18/2011 | ANY | WWM | REVIEW | Active | |
| 05/18/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/01/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 06/02/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 06/02/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/02/2011 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 06/02/2011 | LOREN MAKUS | ENGINEERING | REVIEW | Approved |