Permit Number: T11CM00591
Parcel: 12009001B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM00591
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
02/25/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
02/25/2011 ROBERT SHERRY WATER REVIEW Approved
02/25/2011 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
02/28/2011 DAVID RIVERA ZONING REVIEW Approved
02/28/2011 JASON GREEN ENGINEERING REVIEW Approved
02/28/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T11CM00591
420 E Aviation #100

Electrical plans denied for the following:
1. The units must be considered individual and cut of from each by listed fire walls, currently showing openings between spaces.
2. The grounding systems for each service call for a 3/0 bc to go to existing ground system, the remodel of the existing services will require a new grounding system , unknown what was existing. All grounding systems will be required to be tied together per 250-58.Show the grounds for transformers tied into the system ground.
3. The fault current calculations appear incorrect, please review.
4. Sheet E-3, the feeder for #1 1600 A, 4 sets of 400mcm AL not large enough.
5. Sheet E-3, the feeder for #7 1200 A, 2 sets of 250mcm AL
not large enough.
6. Sheet E-3 , the feeder for #6 2-350mcm together equal 700mcm requiring 2/0 grd per 250.66.
7. Sheet E-3 #8 4-600mcm together total 2400mcm requiring a 3/0 cu grd.
8. Provide an elevation drawing showing the entire 4 services and how they will be located and where.

Ray T Majuta,
Elect Plan CK,PDSD,
City of Tucson,
2/26/11
Ray.Majuta@tucsonaz.gov
02/28/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Passed
02/28/2011 RONALD BROWN ADA REVIEW Passed
02/28/2011 DAVE MANN FIRE REVIEW Approved
02/28/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed