Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T11CM00580
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/03/2011 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | Eric is not available. Lisa Bowers ststed that he clarified that this is not a first tenant in. |
| 03/03/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 03/03/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | Total occupant load is 71 not 49. As per the 2006 IBC chapter 29, two toilets are required for the office and two toilets for the warehouse having a occupant load more than 15. An appeal to the building official is required to lower the warehouse occupancy to 15 or less, in other words allowing a certain percentage of the warehouse occupants share the office toilets. |
| 04/28/2011 | DROBEY1 | WWM | REVIEW | Needs Review |