Permit Number: T11CM00580
Parcel: 14026045A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM00580
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/24/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET IA0.0; BUILDING DATA: FOR 71 OCCUPANTS WITH A B/S1 OCCUPANCY, PER TABLE 2902.1 OF THE 2006 IBC (B OCCUPANCY MOST RESTRICTIVE), 2 RESTROOMS FOR BOTH MEN AND WOMEN ARE REQUIRED (4 TOTAL). ONLY 3 ARE PROVIDED. VERIFY.
2. SHEETS IA1.0 AND IA1.1: THE CITY OF TUCSON REQUIRES THAT ALL LETTERING MUST BE A MINIMUM OF 3/32" IN HEIGHT. REVISE AS REQUIRED.
02/24/2011 JASON GREEN ENGINEERING REVIEW Approved
02/24/2011 ERIC NEWCOMB ADA REVIEW Passed
02/24/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
02/28/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/28/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide a design for the water heater support shelf and it's connection to the building structure.
02/28/2011 ROBERT SHERRY WATER REVIEW Approved
02/28/2011 STEVE SHIELDS ZONING REVIEW Approved
02/28/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
02/28/2011 DAVE MANN FIRE REVIEW Approved
03/02/2011 CPIERCE1 WWM REVIEW Needs Review