Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM00580
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/24/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET IA0.0; BUILDING DATA: FOR 71 OCCUPANTS WITH A B/S1 OCCUPANCY, PER TABLE 2902.1 OF THE 2006 IBC (B OCCUPANCY MOST RESTRICTIVE), 2 RESTROOMS FOR BOTH MEN AND WOMEN ARE REQUIRED (4 TOTAL). ONLY 3 ARE PROVIDED. VERIFY. 2. SHEETS IA1.0 AND IA1.1: THE CITY OF TUCSON REQUIRES THAT ALL LETTERING MUST BE A MINIMUM OF 3/32" IN HEIGHT. REVISE AS REQUIRED. |
| 02/24/2011 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 02/24/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 02/24/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 02/28/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 02/28/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide a design for the water heater support shelf and it's connection to the building structure. |
| 02/28/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/28/2011 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 02/28/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/28/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 03/02/2011 | CPIERCE1 | WWM | REVIEW | Needs Review |