Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM00572
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/24/2011 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 02/24/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 02/24/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Provide total load calculations for the 1600 amp service, including this new L4 Panel. Ray T Majuta C of T, PDSD, Electrical PLan Ck, 2/24/11 Ray.Majuta@tucsonaz.gov |
| 02/24/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/24/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Private shower room needs to accessibility clearances as per Section 1109.2 2. Please provide structural detailing and calculations for all roof top mounted HVAC units. 3. Please provide structural detailing and calculations for the suspended 30 gallon water heater. END OF REVIEW |
| 02/24/2011 | BEV HESTER | ENGINEERING | REVIEW | Approved | |
| 02/24/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show how the water heater platform is connectred to the building structure. 2. The floor drain, as specified, is not suitable for use as an indirect waste receptor and an indirect waste receptor cannot be installed in a bathroom. Reference: section 804.1, UPC 2006. |
| 02/24/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 02/24/2011 | RONALD BROWN | ADA | REVIEW | Passed | |
| 02/24/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 03/03/2011 | DROBEY1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/03/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |