Permit Number: T11CM00572
Parcel: 110035440

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM00572
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/24/2011 STEVE SHIELDS ZONING REVIEW Approved
02/24/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/24/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Provide total load calculations for the 1600 amp service, including this new L4 Panel.

Ray T Majuta
C of T, PDSD,
Electrical PLan Ck,
2/24/11
Ray.Majuta@tucsonaz.gov
02/24/2011 ROBERT SHERRY WATER REVIEW Approved
02/24/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Private shower room needs to accessibility clearances as per Section 1109.2
2. Please provide structural detailing and calculations for all roof top mounted HVAC units.
3. Please provide structural detailing and calculations for the suspended 30 gallon water heater.
END OF REVIEW
02/24/2011 BEV HESTER ENGINEERING REVIEW Approved
02/24/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the water heater platform is connectred to the building structure.
2. The floor drain, as specified, is not suitable for use as an indirect waste receptor and an indirect waste receptor cannot be installed in a bathroom. Reference: section 804.1, UPC 2006.
02/24/2011 DAVE MANN FIRE REVIEW Approved
02/24/2011 RONALD BROWN ADA REVIEW Passed
02/24/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
03/03/2011 DROBEY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/03/2011 DELMA ROBEY OUT TO CUSTOMER Completed