Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM00555
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/04/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
03/07/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
03/08/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. One of the specified fixtures, the Bradley emergency eyewash, requires a minimum pressure of 30 PSI for proper operation. Confirm that the residual pressure at the eyewash will be sufficient for proper operation. . Reference: Sections 310.4 and 608.1, UPC 2006. 2. Clarify the intended use of the 3-compartment sink (FS-0042); any compartments not used for food-handling purposes shall be directly-connected to the sanitary waste system. Reference: Section 801.2.3, UPC 2006. 3. Coordinate the stockroom waste and vent riser (2/PM02) with the stockroom plumbing plans shown on sheet P351 with regard to the fixtures being installed. Show the RPZ correctly installed for the direction of flow. Reference: Section 103.2.3, UPC 2006. 4. Show that floor drain FD-1, located in the stockroom is capable of functioning as an indirect waste receptor for the T&P relief from WH-7 and for the reduced pressure zone backflow preventer serving the evaporative condensing unit (i.e. having the shape and capacity to prevent splashing or flooding). Reference: Sections 603.3.9 and 804.1, UPC 2006. |
03/08/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
03/08/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | The new dehumidifying unit (DHU-01) does not introduce any outdoor air into the building. Show that adequate ventilation is still being supplied to the building. Reference: Sections 102.4 and 401.2, IMC 2006. |
03/17/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM00555 5255 E Broadway Target TI Electrical denied for following: 1. Sheet E601, total amperage for Panel shows 33.9 amps, the actual figure should be 78.3 amps.This also changes the total new amperage for new 600 amp HP-2. R.T. Majuta, Elect Pln Ck, PDSD City of Tucson, 3/22/11, Ray.Majuta@tucsonaz.gov |