Permit Number: T11CM00555
Parcel: 12701008A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM00555
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/04/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
03/07/2011 GERRY KOZIOL WWM REVIEW Approved
03/08/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. One of the specified fixtures, the Bradley emergency eyewash, requires a minimum pressure of 30 PSI for proper operation. Confirm that the residual pressure at the eyewash will be sufficient for proper operation. . Reference: Sections 310.4 and 608.1, UPC 2006.
2. Clarify the intended use of the 3-compartment sink (FS-0042); any compartments not used for food-handling purposes shall be directly-connected to the sanitary waste system. Reference: Section 801.2.3, UPC 2006.
3. Coordinate the stockroom waste and vent riser (2/PM02) with the stockroom plumbing plans shown on sheet P351 with regard to the fixtures being installed. Show the RPZ correctly installed for the direction of flow. Reference: Section 103.2.3, UPC 2006.
4. Show that floor drain FD-1, located in the stockroom is capable of functioning as an indirect waste receptor for the T&P relief from WH-7 and for the reduced pressure zone backflow preventer serving the evaporative condensing unit (i.e. having the shape and capacity to prevent splashing or flooding). Reference: Sections 603.3.9 and 804.1, UPC 2006.
03/08/2011 ROBERT SHERRY WATER REVIEW Approved
03/08/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The new dehumidifying unit (DHU-01) does not introduce any outdoor air into the building. Show that adequate ventilation is still being supplied to the building. Reference: Sections 102.4 and 401.2, IMC 2006.
03/17/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM00555
5255 E Broadway
Target TI

Electrical denied for following:

1. Sheet E601, total amperage for Panel shows 33.9 amps, the actual figure should be 78.3 amps.This also changes the total new amperage for new 600 amp HP-2.

R.T. Majuta,
Elect Pln Ck, PDSD
City of Tucson,
3/22/11,
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
03/24/2011 CPIERCE1 OUT TO CUSTOMER Completed
03/24/2011 SUE REEVES REJECT SHELF Completed