Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2011 RONALD BROWN ADA REVIEW Passed
02/23/2011 GERRY KOZIOL WWM REVIEW Denied NEED TO SUBMIT ORIGINAL DRAWING ISSUED IN 2007 FOR LOFT APTS ON 3RD FL FOR CREDIT EVALUATION
02/23/2011 DAVE MANN FIRE REVIEW Denied Windows on west wall required to one hour rated glass block, per 2006 IFC, section 703 and the 2006 IBC.
03/04/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) PLEASE PROVIDE DETAILS FOR 1 HOUR RATED WALLS INCLUDING FIRE-STOP DETAILS. SIMILARLY PLEASE PROVIDE CUT SHEETS FOR ANY MATERIALS INTENDED TO BE USED FOR WHAT APPEARS TO BE A GLASS FIRE PARTITION.

2) PROVIDE DETAILS FOR 8 FOOT HIGH PARTITIONS.

3) PROVIDE ELEVATIONS FOR SHOWER INDICTATING COMPLIANCE WITH ANSI 117.1.

4) PROVIDE ELEVATIONS FOR KITCHENETTE INDICATING COMPLIANCE WITH ANSI 117.1

5) PLEASE PROVIDE FRAMING DETAILS FOR ALL GLASS WALLS AT KITCHENETTES, CONFERENCE ROOMS, ETC.

6)

7) DETAIL D PP A3.1 CALLS FOR SPLAYED BRACING WIRE FOR GYP-BOARD CEILING. PLEASE SHOW MAXIMUM SPACING OF THESE WIRES.

8) PP A3.1 CALLS FOR 3x8x8 GLASS BLOCKS AT SOME OPENINGS ALONG THE EAST WALL BY THE RESTROOMS. PROVIDE ALL LINTEL AND FRAMING DETAILS FOR REPLACING THE EXISTING BRICK. ALSO PROVIDE CUT SHEETS FOR THE GLASS BLOCK YOU INTEND TO USE.

9) THE LARGE CONFERENCE ROOM REQUIRES 2 EXITS (IBC SECTION 1015).

10) PROVIDE FIRE SAFING DETAILS FOR DUCT PENETRATIONS OF RATED CORRIDOR WALLS PER SECTION 712 & 716 OF THE THE IBC.

11) PROVIDE STRUCTURAL ANALYSIS FOR NEW EQUIPMENT TO BE PLACED ON ROOF.
03/07/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
03/07/2011 LHANLY1 ZONING REVIEW Passed PER ERNIE DUARTE
03/08/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the background of the building to match the current architectural design. Reference: Section 106.3.1, IMC 2006.
2. Show how the fan coils are being connected to the building structure and provide calculations to show that the building structure is not being adversely affected. Reference: Section 302.1, IMC 2006.
3. Show how adequate access is being provided for the equipment located above the corridor ceiling. Reference: Section 306.3, IMC 2006.
03/08/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the background of the building to match the current architectural design. Reference: Section 103.2.3, UPC 2006.
2. The 1" branch piping called out for the water closet flush valves will result in water velocities greater than 8 FPS. Limit the water velocity to less than 8 FPS for the copper piping. Reference: Sections 610.12 and A 6.1, UPC 2006 and IS 3-2003, Section 2.6.
3. Specify how the piping penetrations of the fire-rated partitions comply with Section 1501.1, UPC 2006.
03/08/2011 LHANLY1 WATER REVIEW Approved
03/08/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
03/11/2011 DELMA ROBEY OUT TO CUSTOMER Completed
03/11/2011 SUE REEVES REJECT SHELF Completed