Permit Number: T11CM00519
Parcel: 140420200

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM00519
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/22/2011 DAVID RIVERA ZONING REVIEW Approved
02/22/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide structural drawings and calculations to show that the new evaporative cooler is adequately supported.
02/22/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
02/22/2011 ROBERT SHERRY WATER REVIEW Denied Show that the water meter serving this address is equipped with an approved backflow preventer and that the meter is adequately sized.
02/22/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/22/2011 LOREN MAKUS ENGINEERING REVIEW Approved
02/22/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide a water pressure calculation for this activity.
02/22/2011 DAVE MANN FIRE REVIEW Approved
02/22/2011 ERIC NEWCOMB ADA REVIEW Passed
02/22/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/02/2011 CPIERCE1 WWM REVIEW Needs Review