Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM00519
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/22/2011 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 02/22/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide structural drawings and calculations to show that the new evaporative cooler is adequately supported. |
| 02/22/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/22/2011 | ROBERT SHERRY | WATER | REVIEW | Denied | Show that the water meter serving this address is equipped with an approved backflow preventer and that the meter is adequately sized. |
| 02/22/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/22/2011 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 02/22/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide a water pressure calculation for this activity. |
| 02/22/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 02/22/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 02/22/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/02/2011 | CPIERCE1 | WWM | REVIEW | Needs Review |