Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM00504
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/17/2011 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 02/17/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Clearly identify the rooftop units referenced in the ventilation calculations and state the balancing criteria in CFM (not in %). |
| 02/17/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Electrical comments: The electrical plan has been denied for the following, Previous plans do not show a tap to the line side of the meter of the existing 600 anp service, last plans show Panel C feeding of existing panel B. These plans show an existing meter already in. Ray T Majuta Elect Pln CK,PDSD, City ofTucson 2/17/11 |
| 02/17/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/17/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/17/2011 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 02/17/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 02/17/2011 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/17/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 02/17/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/23/2011 | CPIERCE1 | ENGINEERING | REVIEW | Needs Review |