Permit Number: T11CM00504
Parcel: 13819032C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM00504
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/17/2011 MICHAEL ST. PAUL ZONING REVIEW Approved
02/17/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Clearly identify the rooftop units referenced in the ventilation calculations and state the balancing criteria in CFM (not in %).
02/17/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Electrical comments: The electrical plan has been denied for the following,

Previous plans do not show a tap to the line side of the meter of the existing 600 anp service, last plans show Panel C feeding of existing panel B. These plans show an existing meter already in.


Ray T Majuta
Elect Pln CK,PDSD, City ofTucson
2/17/11
02/17/2011 ROBERT SHERRY WATER REVIEW Approved
02/17/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/17/2011 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
02/17/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/17/2011 MARTIN BROWN FIRE REVIEW Approved
02/17/2011 ERIC NEWCOMB ADA REVIEW Passed
02/17/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/23/2011 CPIERCE1 ENGINEERING REVIEW Needs Review