Permit Number: T11CM00498
Parcel: 10408090D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM00498
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/16/2011 MICHAEL ST. PAUL ZONING REVIEW Approved
02/16/2011 PAUL MACHADO ENGINEERING REVIEW Approved
02/16/2011 ERIC NEWCOMB ADA REVIEW Passed
02/16/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/16/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/17/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show that the building addition meets the requirements of the 2006 IECC.
2. Revise the size of the common condensate drains as shown in section 307.2.2, IMC 2006 as amended by the City of Tucson.
3. Clarify how an exhaust fan is able to be used to supply outside air to the new spaces.
02/17/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
02/17/2011 ROBERT SHERRY WATER REVIEW Approved
02/17/2011 MARTIN BROWN FIRE REVIEW Approved
02/17/2011 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
02/17/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Electrical comments:
1. Indicate circuit numbers on floor power plan.
2. One FC unit has a 15 breaker in the panel and 30 amp on the other, The feeders to the CU should be # 10.
3. Where will the condensate pump be installed, if above the cieling it may not be allowed, if pump uses a cord to connect, (2005 NEC 400.8.2)

Ray Majuta,
Elect Plan Ck, City of Tucson,
2/17/11