Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM00498
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/16/2011 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 02/16/2011 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 02/16/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 02/16/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/16/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/17/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show that the building addition meets the requirements of the 2006 IECC. 2. Revise the size of the common condensate drains as shown in section 307.2.2, IMC 2006 as amended by the City of Tucson. 3. Clarify how an exhaust fan is able to be used to supply outside air to the new spaces. |
| 02/17/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 02/17/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/17/2011 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/17/2011 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 02/17/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Electrical comments: 1. Indicate circuit numbers on floor power plan. 2. One FC unit has a 15 breaker in the panel and 30 amp on the other, The feeders to the CU should be # 10. 3. Where will the condensate pump be installed, if above the cieling it may not be allowed, if pump uses a cord to connect, (2005 NEC 400.8.2) Ray Majuta, Elect Plan Ck, City of Tucson, 2/17/11 |