Permit Review Detail
Review Status: Completed
Review Details: SITE
Permit Number - T11CM00480
Review Name: SITE
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/15/2011 | DAVE MANN | FIRE | REVIEW | Denied | Fire Comments: Show calculations for allowable area. Building was originally VB/AS with 60 foot yards. This would eliminate one yard. |
| 02/16/2011 | PAUL MACHADO | ENGINEERING | REVIEW | Denied | To: Wayne Swan, Intertech Arch. DATE: February 16, 2011 6089 E. Grant Road Tucson, Arizona 85712 Subject:Modular Mining Systems Inc.,3289 E. Hemisphere Lp Site plan T11CM00480 (First Review) T15S, R14E, Section 09 RESUBMITTAL REQUIRED: Site Plan and Drainage Statement. The Site Plan (SP) and Drainage Statement (DS) cannot be approved as submitted. Please address the following review comments prior to the next submittal. Site Plan: 1. Please include a response letter to the comments along with the corrected copies of the SP. 2. Please label lot dimensions and bearings per D.S. 2-02.2.1.5 3. Please provide Drainage patterns and finished grades per D.S. 2-02.2.1.16. 4. Please list estimated cut & fill quantities per D.S. 2-02.2.1.17. 5. Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23. 6. Show Site plan number (T11CM00480) on all sheets per D.S. 2-02.2.1.29. 7. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks including any other site drainage as well. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers and/or sidewalk scuppers have not yet been decided, a general note indicating sidewalk scuppers will be used when the roof drain/sidewalk scupper locations have been designed and located and that the 10-year flow must be conveyed under any other sidewalks and/or pedestrian paths will suffice. 8. A floodplain use permit may be required. 9. Add note: "Depress all landscaped areas 6" maximum for water harvesting". 10. Remove the "Code Check" section on the first sheet and replace with the corrected information. Drainage Statement: 1. Please include a response letter to the comments along with the corrected copies of the DS. 2. A Drainage Statement is a brief description of drainage conditions applicable for a site which are not affected by 100 year flows of 100 cfs, of more……per S.M.D.D.F.M., chap. II, 2.1.2. The DS must be submitted along with the site plan and accepted with the approval of the grading plan. 3. The content and format of the Drainage Statement should follow S.M.D.D.F.M., chap. II, 2.2. 4. Show the project address or administration address on the cover sheet of the DS. If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov Paul P. Machado Senior Engineering Associate City of Tucson - Planning and Development Services Department 201 N. Stone Avenue P.O. Box 27210 Tucson, Arizona 85726-7210 (520) 837-4932 office (520) 879-8010 fax C:/3289 E. Hemisphere Lp. Site.doc |
| 02/24/2011 | RBROWN1 | ADA | REVIEW | Passed | |
| 03/02/2011 | ANDREW CONNOR | NPPO | REVIEW | Passed | |
| 03/10/2011 | DAVID RIVERA | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: David Rivera Principal Planner PROJECT: T11CM00480 3289 E Hemisphere Loop Site Plan (Principal use - not clear) TRANSMITTAL DATE: March 10, 2011 COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. 1. List the principal use(s) on sheet two under LUC code data section or add it the cover sheet under the requested code data info, (LUC development criteria) 2. Demonstrate maneuverability into and out of the loading areas. See additional engineering comments related to this comment. 3. A minimum five-foot striped pedestrian refuge area is required adjacent to the new building area if access is only for employees otherwise a five-foot pedestrian refuge area which includes a four-foot concrete sidewalk is required if the public will have access to this area.. 4. Clarify if enclosing the center courtyard into an employee lounge was approved as part of previous site submittal or improvement. The copy of the last approved site plan indicates and open courtyard in this location. 5. Include copies of the cover sheet that provides the code data which should include the previously approved parking calculations. Typically the parking calculations are based on the principal use but I have been given direction (based on the minimal expansion) to approve as noted if this is how the previous plan was approved. 6. Revise the parking space details drawing to indicate that the wheel stops are 2.5 feet from the front or wheel side (not the center) of the bumper to the front of the parking space. 7. Label the adjacent zoning to the north, south and west. 8. Draw and label the covered parking. If you have any questions about this transmittal, please call David Rivera, (520) 791-5608. C:\planning\cdrc\DSD\T11CM00480sp.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents |
| 03/11/2011 | RONALD BROWN | H/C SITE | REVIEW | Approved | |
| 03/11/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Revise the site drawing to include the following information: a. the location and size of the water meter b. the location of the main water lines and fire hydrants c. the location of the gas meter (if one exists or is planned) d. the location and size of the public sanitary sewer e. the location of the building connection to the public sewer f. the location, invert, and rim elevation of the upstream and downstream manholes and cleanouts g. the first floor elevation for the building Reference: City of Tucson Development Standard No. 2-01.0.0, Section 3.8 D and Section 103.2.3, UPC 2006. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/04/2011 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 04/04/2011 | SUE REEVES | REJECT SHELF | Completed |