Permit Number: T11CM00463
Parcel: 10604073A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM00463
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/11/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/15/2011 LOREN MAKUS ENGINEERING REVIEW Approved
08/15/2011 STEVE SHIELDS ZONING REVIEW Approved
08/22/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved; the minimum code-compliant room temperature is not 55 degrees Fahrenheit. Show how the existing HVAC equipment is capable of maintaining a minimum temperature of 68 F in the interior spaces intended for occupancy on a design heating day (32 F). Reference: Sections 309.1 and 312.1, IMC 2006.
08/22/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the installation of the sink; on sheet A1 it is shown with a 3" waste and a 2-way cleanout but on sheet TS1 the site plan indicates that a 2" waste from the sink connects to the 4" building sewer.
2. Comment not addressed; no backwater valve appears to have been installed. The first floor elevation is lower than the rim elevation of the next upstream manhole; provide a backwater valve.
08/30/2011 CAGUILA1 WWM REVIEW Needs Review