Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM00463
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/11/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/15/2011 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 08/15/2011 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 08/22/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not resolved; the minimum code-compliant room temperature is not 55 degrees Fahrenheit. Show how the existing HVAC equipment is capable of maintaining a minimum temperature of 68 F in the interior spaces intended for occupancy on a design heating day (32 F). Reference: Sections 309.1 and 312.1, IMC 2006. |
| 08/22/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the installation of the sink; on sheet A1 it is shown with a 3" waste and a 2-way cleanout but on sheet TS1 the site plan indicates that a 2" waste from the sink connects to the 4" building sewer. 2. Comment not addressed; no backwater valve appears to have been installed. The first floor elevation is lower than the rim elevation of the next upstream manhole; provide a backwater valve. |
| 08/30/2011 | CAGUILA1 | WWM | REVIEW | Needs Review |