Permit Number: T11CM00463
Parcel: 10604073A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM00463
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/25/2011 DAVE MANN FIRE REVIEW Approved
07/25/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how the addition of the new reception will affect the existing building HVAC with regard to ventilation and heating.
2. Provide ventilation calculations for the addition.
3. Show that the addition meets the envelope energy criteria of IECC 2006.
07/25/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
07/25/2011 ROBERT SHERRY WATER REVIEW Approved
07/25/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET TS1; CODE STUDY/PROJECT DATA: THE CODE STUDY INDICATES BUILDING 1 AREA OF 1640 SF, WHILE THE PROJECT DATA INDICATES 1606 SF. CLARIFY.
2. SHEET TS1; CODE STUDY: PROVIDE THE OCCUPANT LOAD FOR BUILDING 1 AND THE ADDITION.
3. SHEET TS1: PROVIDE CALCULATIONS FOR PLUMBING FIXTURES (RESTROOMS, SERVICE SINK, DRINKING FOUNTAINS) OR VERBIAGE FOR TRAVEL DISTANCES TO THESE ITEMS.
4. SHEET A1; DETAILS: THE TITLE VERBIAGE FOR 3 DETAILS AT THE BOTTOM OF THE SHEET IS MISSING. PROVIDE.
5. SHEET A1; FLOOR PLAN: BUILDING SECTION 6/A1 IS NOT CORRECT. REVISE.
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
07/25/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a cleanout for the new sink.
2. The first floor elevation is lower than the rim elevation of the next upstream manhole; provide a backwater valve.
3. Provide gutters for the roof.
07/25/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
07/25/2011 ERIC NEWCOMB ADA REVIEW Passed
08/11/2011 CPIERCE1 WWM REVIEW Needs Review
08/11/2011 CPIERCE1 ZONING REVIEW Needs Review
08/11/2011 CPIERCE1 ENGINEERING REVIEW Needs Review