Permit Number: T11CM00456
Parcel: 123030300

Address:
2838 E ELM ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM00456
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2012 CAGUILA1 BUILDING-RESIDENTIAL REVIEW Needs Review
02/25/2011 MICHAEL ST. PAUL ZONING REVIEW Denied CDRC TRANSMITTAL

FROM: Michael St.Paul: Planning Technician


PROJECT:
T11CM00456
2838 East Elm Street
Carport addition to workshop and guest house


TRANSMITTAL: February 25, 2011


COMMENTS: The following comments are for the purpose of applying for a variance before the Board of Adjustment.


The site is in the R-1 Zone (LUC Section 2.3.4.2.A.1.). The Development Designator is "G" (LUC Section 3.2.3.1.B). The Perimeter Yard Indicator is AA (LUC Section 3.2.6.4).

The request for variance is for a reduced setback and driveway length along the east property line. The request for the variance also includes reductions in the side yard setbacks. The minimum sideyard setback is ten (10) feet to the property line (LUC Section 3.2.6.5.A). The minimum driveway length is eighteen (18) feet from the front of the carport to the property line (LUC Section 3.2.6.5.B.2.a). The proposed setback is one (1) foot to the property line.