Permit Number: T11CM00429
Parcel: 13323193C

Address:
750 N KOLB RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM00429
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/08/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide information about the complete existing gas piping system so the new addition can be evaluated.
2. Detail 4/M.2 references additional plumbing drawings for the drain route and termination. Provide the needed information.
02/08/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the exhaust duct to provide a velocity of at least 1500 FPM.
2. Revise detail 1/M.2 to show how this hood is to be supported from the building structure; generic details are not acceptable.
02/08/2011 ROBERT SHERRY WATER REVIEW Approved
02/08/2011 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
02/09/2011 MARTIN BROWN FIRE REVIEW Approved
02/09/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
02/09/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/09/2011 ERIC NEWCOMB ADA REVIEW Passed
02/09/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/10/2011 JASON GREEN ENGINEERING REVIEW Approved
02/10/2011 DAVID RIVERA ZONING REVIEW Approved