Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM00429
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/08/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide information about the complete existing gas piping system so the new addition can be evaluated. 2. Detail 4/M.2 references additional plumbing drawings for the drain route and termination. Provide the needed information. |
| 02/08/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the exhaust duct to provide a velocity of at least 1500 FPM. 2. Revise detail 1/M.2 to show how this hood is to be supported from the building structure; generic details are not acceptable. |
| 02/08/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/08/2011 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 02/09/2011 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/09/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/09/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/09/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 02/09/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/10/2011 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 02/10/2011 | DAVID RIVERA | ZONING | REVIEW | Approved |